Application of Cohen-Coon Method for Tuning of pH Controller Parameters in Neutralization Tank, Waste Water Treatment Unit
Profiyanti Hermien Suharti, Khalimatus Sa'diyah
Abstract
Wastewater generated in industry should be treated, in order to meet the standards set by the Government. pH became important parameters in the process of wastewater treatment. One of waste in industrial synthetic fibers contain ions that make pH of wastewater ranged from 2 to 3. The value of the threshold for the pH of the wastewater, based on regulation of the Minister of environment, ranged from 6 to 9. The main process to achieve this standar was the neutralization process. In order to fulfilment the pH target, pH controller has been used to monitor the pH at neutralization tank. pH controller which is used is a type of PID (proportional, integral, derivative) controller. The PID parameter that used in the controller are proportional gain (Kc) 10, integral time (τi) 1 minutes and 10 second as derivative time (τD). This parameter yields an oscillation response. This research aims to get the optimum PID parameters that can be applied to keep wastewater pH around 7. The experiment results show that the parameters of the PID controller Kc = 0.251, τi = 151 second = 2.51 minutes and τD = 12.5 second, had better performance than the PID controller parameters used previously.
Babu, R., & Swarnalath, R. (2017). Comparison of Different Tuning Methods for pH Neutralization in Textile Industry. Journal of Applied Sciences, 17(3), pp. 142–147. https://doi.org/10.3923/jas.2017.142.147
Hermawan, Y. D. (2010). Implementation of Process Reaction Curve for Tuning of Temperature Control Parameters in A 10 L Stirred Tank Heater, Journal of Materials Science and Engineering A 1 (2011). pp.572-577. ISSN 1934-89591–6.
Hermawan, Y. and G. Haryono. (2012). Dynamic Simulation And Composition Control In A 10 L Mixing Tank. Reaktor, 14(2), pp. 95-100, Nov. 2012. https://doi.org/10.14710/reaktor.14.2. 95-100
Kumar, D. D., & Deepika, D. (2014). Performance comparison of pH Neutralization process among different tunings of conventional controllers. Applied Mechanics and Materials 573, pp. 260–266. https://doi.org/10.4028/www.scientific.net /AMM.573.260
Rice, R. C. (2010). PID Tuning Guide A Best-Practices Approach to Understanding and Tuning PID Controllers First Edition Simplifying PID Control, Optimizing Plant Performance. Retrieved from https://web-material3.yokogawa.com/Yokogawa_ PID_Tuning_Guide_-_csTuner.pdf?_ga=1.61113583 .296607337.1493113296
Wahid, A., & Abdillah, F. (2014). Pengendalian pH Limbah Cair Laboratorium Departemen Teknik Kimia UI Menggunakan Pengendali PID Linear Pada Mini Plant WA921. SINERGI 18(2), Juni 2014, pp. 85–91.